[ Prev ]    Page:   1    2    3    4    5    6    7    8    [ Next ]

PDF version for print


Specifications

ECO series consists of UniPanel (main panel), Base Connector,Central Cap, Flank Cap, Ramp, Sound Attenuation Blanket and all necessary accessories. System when assembly are suitable for used in general office buildings and school, except areas designed for fire escape or lifts.

 

Module: 600mm x 600mm (24" x 24")

 

System

CA-600R

CA-500R

CA-400R

Height

60mm (2.36")

50mm (1.57")

40mm (1.57")

Cable Trench width

90mm (3.54")

90mm (3.54")

90mm (3.54")

Cable Trench clearance

55mm (2.16")

45mm (1.77")

35mm (1.37")

 

Main Components:
UniPanel: made of fire retard, recycled polypropylene.
CA-611R: size 510 x 510 x 60mm (20.08" x 20.08" x 2.36")
CA-511R
: size 510 x 510 x 50mm (20.08" x 20.08" x 1.97")
CA-411R
: size 510 x 510 x 40mm (20.08" x 20.08" x 1.57")

Base Connector: Size 169 x 169 x 15mm (6.65" x 6.65" x 0.59") Made of recycled polycarbonate plus ABS.

Central Cap: Size 148 x 148mm (5.82" x 5.82"),
2.3 mm (0.09") thick steel, re-enforced ribs corrosion resistance treatment by electro-deposition, black

Flank Cap: Size 223 x 119.7mm (8.78" x 4.71"),
2.3 mm (0.09") thick steel, re-enforced ribs corrosion resistance treatment by electro-deposition, black

Sound Attenuation Blanket: 2.0mm (0.08") thickness.

 

Accessories:
Ramp, Starting Cap, Edge Rail, Aluminum Ramp Rail, Aluminum Free Standing, Exit-Cap, Edge Trimmer, etc., to support quick and efficient installation by least cutting at perimeters.

 

Surface floor covering: on top of ECO series
Commercial carpet tile: such as Milliken, Interface, Burmatex...
Commercial rate vinyl tile: thickness > 4.0 mm
Hard floorings such as marble, granite, wood, are not suitable.

Tests

 

Fire Retard
UniPanel: Meet NFPA 253 class A rating as test in accordance with ASTM E-648 Critical Radiant Flux.
Meet BS 476, Part 7, B2
Central Cap: non-conbustible
Flank Cap:  non-conbustible

 

Concentration Load:
Test in accordance with ASTM E-196 (2" plate)
UniPanel CA-611R: 400 kg < 2.5 mm depression
UniPanel CA-511R: 360 kg < 2.5 mm depression
UniPanel CA-411R: 360 kg < 2.5 mm depression
Central Cap: 300 kg < 2.0 mm depression
Flank Cap:  300 kg < 2.0 mm depression

 

Concentration Ultimate Load:
CA-611R UniPanel > 700 kg
CA-511R UniPanel > 600 kg
CA-411R UniPanel > 600 kg

 

UniForm Ultimate Load:
CA-611R UniPanel > 200 psi
CA-511R UniPanel > 150 psi
CA-411R UniPanel > 150 psi

 

Warranty: 5 years warranty (except when product is subject to abuse, negligence, abnormal use and not under Netfloor's installation instruction)

 

In pursuing of quality improvement, the manufacturer reserves the right to vary specifications without prior notice.

 


 

Patent granted

 

Japan: Utility Model No. 3032638
Australia: Invention Patent No. 679415
France: Invention Patent No. 97 99 255
Taiwan: Invention Patent No. 127700
South Africa: Invention Patent No. 97/020
Patent pending: All other industrial nations

USA: Invention Patent No. 5.630.300
Germany: Utility Model No, 29520105.5
UK: Invention Patent No. 2309042
China: Utility Model No. ZL96200625.4

   

 